Operation and maintenance
August 2019
Perform a 4-20 mA output trim with AMS Device Manager
Complete the following steps to perform a digital-to-analog trim with AMS Device
Manager.
Procedure
1. Right-click the device. Under the Method drop down menu, move the cursor over
2. Select Digital to Analog Trim.
3. Follow the screen prompts to perform a 4-20 mA output trim.
Perform a 4-20 mA output trim with LOI
Go to EXTENDED MENU → CALIBRAT → ANALOG TRIM.
Figure 5-6: 4-20 mA Output Trim Using LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
5.6.2
Performing digital-to-analog trim (4-20 mA output trim)
using other scale
The scaled 4-20 mA output trim command matches the 4 and 20 mA points to a user
selectable reference scale other than 4 and 20 mA (for example, two to ten volts if
measuring across a 500 Ω load or 0 to 100 percent if measuring from a Distributed Control
System (DCS)).
To perform a scaled 4-20 mA output trim, connect an accurate reference meter to the
transmitter and trim the output signal to scale as outlined in the output trim procedure.
96
Calibrate and select Analog Calibration.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
Reference Manual
00809-0100-4007
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
FACTORY RECALL
BACK TO MENU
EXIT MENU
Rosemount 3051