4.7.5

Related devices

1. Devices used to switch the counting direction of 1-phase 1-counting input counters
Type
1-phase
1-counting input
2. Devices used to monitor the counting direction of 1-phase 2-counting input counters and
2-phase 2-counting input counters
Type
1-phase
2-counting input
2-phase
2-counting input
3. Devices used to switch the high speed counter function
Device No.
Contact for changing function
M8388
of high speed counter
M8389
M8390
M8391
Function switching
M8392
device
M8198
M8199
4. Operation status of hardware counters and software counters
Device No.
Name
*1
M8380
*1
M8381
*1
M8382
*1
M8383
Operation
status
*1
M8384
*1
M8385
*1
M8386
*1
M8387
*1.
Cleared when the PLC mode switches from STOP to RUN.
Counter No.
Specifying device
C235
M8235
C236
M8236
C237
M8237
C238
M8238
C239
M8239
C240
M8240
C241
M8241
C242
M8242
C243
M8243
C244
M8244
C245
M8245
Counter No.
Monitoring device
C246
M8246
C247
M8247
C248
M8248
C249
M8249
C250
M8250
C251
M8251
C252
M8252
C253
M8253
C254
M8254
C255
M8255
Name
Changes the function of high speed counter.
Switches the logic of the external reset input.
(For details, refer to Subsection 4.7.6.)
Switches the function of C244. (For details, refer to Subsection 4.7.7.)
Switches the function of C245. (For details, refer to Subsection 4.7.7.)
Switches the function of C248 and C253.
(For details, refer to Subsection 4.7.7.)
Switches the edge count (between 1 and 4) of C251, C252 and C254.
(For details, refer to Subsection 4.7.8.)
Switches the edge count (between 1 and 4) of C253, C255 and C253 (OP).
(For details, refer to Subsection 4.7.8.)
Operation status of C235, C241, C244, C246, C247, C249, C251, C252 or C254
Operation status of C236
Operation status of C237, C242 or C245
Operation status of C238, C248, C248(OP), C250, C253 or C255
Operation status of C239 or C243
Operation status of C240
Operation status of C244(OP)
Operation status of C245(OP)
Up-counting
Down-counting
OFF
Up-counting
Down-counting
OFF
Description
Description
4 Devices in Detail
4.7 High Speed Counter [C]
ON
ON
ON
OFF
Software
Hardware
counter
95
1
2
3
4
5
6
7
8
9
10