Extension registers (R)
inside built-in RAM memory
S
+1
S
S
+2
+2047
S
*1 "n" points are written (transferred) in each operation cycle.
• Extension file registers are written in units of sector (2048 points).
The table below shows the head device number in each sector:
Sector
number
Sector 0
R0
Sector 1
R2048
Sector 2
R4096
Sector 3
R6144
Sector 4
R8192
Sector 5
R10240
Sector 6
R12288
Sector 7
R14336
• If "n" is set to "0", it is handled as "2048" when the instruction is executed.
• When writing (transfer) of 2048 points is finished, execution of the instruction is completed and the
instruction execution complete flag M8029 turns ON.
• The number of already written points is stored in
2. Related device
Device
number
Instruction
M8029
complete flag
Cautions
1. Cautions on writing data to a memory cassette
Memory cassettes adopt flash memory. Note the following contents when writing data to extension file
registers in a memory cassette with the FNC291 instruction.
• It takes 50 to 60 ms to write 2048 points. If "n" is set to K0 or K2048, the operation cycle for executing this
instruction becomes longer by 50 to 60 ms.
If the operation cycle is severely affected, write data in two or more operation cycles.
When writing data in two or more operation cycles, set "n" in the range from K1 to K1024.
Extension file registers (ER)
*1
inside memory cassette
Write
(transfer)
E
E
E
E
Head device
Written device range
number
ER0 to ER2047
ER2048 to ER4095
ER4096 to ER6143
ER6144 to ER8191
ER8192 to ER10239
ER10240 to ER12287
ER12288 to ER14335
ER14336 to ER16383
→ For the instruction execution complete flag use method, refer to Subsection 6.5.2.
Name
When execution of the target instruction is completed, the instruction execution
complete flag M8029 turns ON.
execution
In a program, however, there may be two or more instructions which can use the
flag M8029. To avoid confusion, make sure to use the NO contact of this flag
immediately under SAVER instruction so that this flag works only for SAVER
instruction.
33 Extension File Register Control – FNC290 to FNC299
S
+1
S
S
+2
+2047
S
Sector
Head device
number
number
Sector 8
R16384
Sector 9
R18432
Sector 10
R20480
Sector 11
R22528
Sector 12
R24576
Sector 13
R26624
Sector 14
R28672
Sector 15
R30720
.
D
Description
33.2 FNC291 – SAVER / Save to ER
Written device range
ER16384 to ER18431
ER18432 to ER20479
ER20480 to ER22527
ER22528 to ER24575
ER24576 to ER26623
ER26624 to ER28671
ER28672 to ER30719
ER30720 to ER32767
31
32
33
34
35
36
37
A
B
C