Mitsubishi FX3U Series Programming Manual page 821

Hide thumbs Also See for FX3U Series:
Table of Contents

Advertisement

FX
/FX
Series Programmable Controllers
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Number and name
Memory Information
[D]8101
1 6
PLC type and
FX
3U
system version
FX
3UC
2 ...... 2K steps
4 ...... 4K steps
[D]8102
8 ...... 8K steps
16 .... 16K steps
64 .... 64K steps
[D]8103
Not used
[D]8104
Identity code for function extension memory
Version of function extension memory
[D]8105
(Version 1.00 = 100)
[D]8106
Not used
[D]8107
Number of registered device comments
[D]8108
Number of special function units/blocks connected
*1.
Available in Ver. 3.00 or later.
Output Refresh Error (Refer to Chapter 37 for details.)
[D]8109
Y number where output refresh error occurs
[D]8110
Not used
[D]8111
Expansion Board Dedicated to FX
[D]8112
FX
-2AD-BD: Digital value of ch1
1N
[D]8113
FX
-2AD-BD: Digital value of ch2
1N
D 8114
FX
-1DA-BD: Digital value to be output
1N
[D]8115 to [D]8119
Not used
RS (FNC 80) and Computer Link [ch1] (Refer to Data Communication Edition for details.)
RS (FNC 80) instruction and computer link [ch1]
*2
D 8120
Communication format setting
*2
Computer link [ch1] Station number setting
D 8121
RS (FNC 80) instruction:
*3
[D]8122
Remaining points of transmit data
RS (FNC 80) instruction:
*3
[D]8123
Monitoring receive data points
D 8124
RS (FNC 80) instruction: Header <Default: STX>
D 8125
RS (FNC 80) instruction: Terminator <Default: ETX>
[D]8126
Not used
Computer link [ch1]
D 8127
Specification of on-demand head device register
Computer link [ch1]
D 8128
Specification of on-demand data length register
RS (FNC 80) instruction, computer link [ch1]
*2
D 8129
Time-out time setting
*2.
Latch (battery backed) device
*3.
Cleared when PLC switches from RUN to STOP.
Content of register
1 0 0
BCD converted value
/
Version 1.00
and FX
1S
1N
36 Operation of Special Devices (M8000 -, D8000 -)
36.1 Special Device List (M8000 -, D8000 -)
Applicable model
Correspond-
FX
FX
ing special
FX
3U
3UC
1S
device
64
64
2
M8104
M8107
M8109
M8112
M8113
M8112
M8122
M8123
M8126 to
M8129
31
FX
FX
FX
FX
1N
2N
1NC
2NC
32
4
4
33
8
8
8
8
16
16
*1
*1
*1
*1
34
35
36
37
819
A
B
C

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3uc seriesMelsec-f

Table of Contents