Mitsubishi FX3U Series Programming Manual page 125

Hide thumbs Also See for FX3U Series:
Table of Contents

Advertisement

FX
/FX
Series Programmable Controllers
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Operations
Pointer for
interrupt
I001
Pointer for
interrupt
I101
2. Pointers for timer interrupt: 3 points
The PLC executes an interrupt routine program at every specified interrupt cycle time (1 to 99 ms).
Use these pointers for control requiring cyclic processing without regard to the operation cycle of the PLC.
Input No.
I6
I7
I8
*1.
Cleared when the PLC mode switches from RUN to STOP.
Caution
It is recommended to set the timer interrupt time to 10 ms or more. When the timer interrupt time is set to 9
ms or less, the timer interrupt processing may not be executed at an accurate cycle in the following cases:
• When the processing time of the interrupt program is long
• When an instruction requiring long processing time is used in the main program
FNC 04
EI
Interrupt enabled
range
FNC 06
FEND
Rising edge of X000 is detected
Interrupt routine [1]
FNC 03
IRET
Rising edge of X001 is detected
Interrupt routine [2]
FNC 03
IRET
END
→ For the details of timer interrupt function, refer to Section 35.5.
Interrupt cycle (ms)
An integer in the range from 1 to 99 is put in "
name.
Ex: I610 = Timer interrupt at every 10 ms
4.11 Pointer [P and I]
Interrupt is usually disabled in the PLC.
If interrupt is enabled by EI instruction, when
X000 or X001 turns ON while a program is
scanned, the PLC executes the interrupt
routine [1] or [2], and then returns to the main
program by IRET instruction.
Make sure to program a pointer for interrupt
(I***) as a label after FEND instruction.
Interrupt disabling flag
" portion of the pointer
4 Devices in Detail
1
2
3
4
5
6
*1
M8056
*1
M8057
*1
M8058
7
8
9
10
123

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3uc seriesMelsec-f

Table of Contents