4) Parallel recombination and selective branch
<SFC program>
20
X000
1
TRAN
103
Dummy state
X001
2
TRAN
40

34.2.7 Program examples

Examples of single flows
1. Example of flicker circuit
• When the PLC mode is changed from STOP to RUN, the state relay S3 is driven by the initial pulse
(M8002).
• The state relay S3 outputs Y000. 1 second later, the ON status transfers to the state relay S20.
• The state relay S20 outputs Y001. 1.5 seconds later, the ON status returns to the state relay S3.
Y000
Y001
1
second
30
X002
3
TRAN
50
Step
number
1.5
seconds
<Step ladder>
STL
STL
X000
SET
STL
X001
SET
X002
SET
<Step ladder>
M8002
SET
S3
0
Initial pulse
STL
S3
3
Y000
4
T0
T0
SET
S20
8
STL
S20
11
Y001
12
T1
T1
S3
16
RET
19
END
20
34 SFC Program and Step Ladder
34.2 Step Ladder
<List program>
STL
S20
S20
STL
S30
S30
LD
X000
SET
S103
S103
STL
S103
LD
X001
S103
SET
S40
LD
X002
S40
SET
S50
S50
<List program>
Step
0
LD
M8002
number
1
SET
S3
3
STL
S3
4
OUT
Y000
5
OUT
T0 K10
8
LD
T0
K10
9
SET
S20
11
STL
S20
12
OUT
Y001
13
OUT
T1 K15
16
LD
T1
17
OUT
S3
19
RET
K15
20
END
31
32
33
34
35
36