Mitsubishi FX3U Series Programming Manual page 774

Hide thumbs Also See for FX3U Series:
Table of Contents

Advertisement

FX
/FX
Series Programmable Controllers
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
2. Example of selective recombination
Do not use MPS, MRD, MPP, ANB and ORB instructions in a transfer processing program with branches and
recombination.
Even in a load driving circuit, MPS instructions cannot be used immediately after STL instructions.
Pay attention to the programming order so that a branch line does not cross a recombination line.
<SFC program>
29
X010
1
50
<Step ladder>
STL
STL
STL
STL
X010
SET
STL
X011
SET
STL
X012
SET
Before recombination, first program the drive processing of state relays.
After that, program only the transfer processing to recombination state relays.
This rule should be observed to enable inverse conversion into an SFC program.
772
39
Y010
X011
2
TRAN
S29
Y010
S39
Drive
processing
Y011
S49
Y012
S29
S50
S39
Transfer
processing
S50
S49
S50
49
Y011
X012
3
TRAN
<List program>
STL
S29
OUT
Y010
STL
S39
OUT
Y011
STL
S49
OUT
Y012
STL
S29
LD
X010
SET
S50
STL
S39
LD
X011
SET
S50
STL
S49
LD
X012
SET
S50
34 SFC Program and Step Ladder
34.2 Step Ladder
Y012
TRAN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3uc seriesMelsec-f

Table of Contents