Profibus Cable Lengths; Rules For Routing Profibus Cables - Siemens SIMOTION D410 Manual

Hide thumbs Also See for SIMOTION D410:
Table of Contents

Advertisement

6.9.3

PROFIBUS cable lengths

Cable lengths and baud rate
The baud rate determines the cable length of a subnet segment.
Table 6-8
Baud rate
19.6 to 187.5 Kbits/s
500 Kbits/s
1.5 Mbits/s
3 to 12 Mbit/s
With isolated interface
1)
Greater cable lengths
If you must realize greater cable lengths than permitted in one segment, you must use RS 485
repeaters. The maximum possible cable lengths between two RS 485 repeaters correspond
to the cable length of a segment. You can connect up to nine RS 485 repeaters in a series.
Note that an RS 485 repeater must be counted as a subnet node when determining the total
number of nodes to be connected. This is true even if the RS 485 repeater is not assigned its
own PROFIBUS address.
6.9.4

Rules for routing PROFIBUS cables

Routing bus cables
When routing the PROFIBUS cable, you must avoid:
● Twisting
● Stretching
● Squeezing
Boundary conditions
You must pay attention to the following boundary conditions when routing the bus cable for
indoor use (dA = external cable diameter):
Table 6-9
Features
Bending radius for a single bend
Bending radius for multiple bends
SIMOTION D410
Manual, 04/2014
6.9 Connecting the PROFIBUS DP interface (410 DP only)
Permitted cable length of a subnet segment for specific baud rates
Boundary conditions for routing of PROFIBUS cables
Max. cable length of a segment (in m)
1,000
1)
400
200
100
Boundary conditions
80 mm (10 x dA)
160 mm (20 x dA)
Connecting
79