Siemens SIMOTION D410 Manual page 37

Hide thumbs Also See for SIMOTION D410:
Table of Contents

Advertisement

Operating
S1
S2
mode
STOPU
110 / 101 / 011
(two switches =
ON)
STOP
100 / 010 / 001
(one switch = ON)
MRES
0
0
(no switches = ON)
Note
In the "RUN" setting (S1, S2, and S3 = ON; S4 to S7 = OFF), you can even control the
SIMOTION D410 operating mode using the SIMOTION SCOUT engineering system. This
means that it is not necessary to adjust the DIP switch in order to change the operating mode.
SIMOTION D410
Manual, 04/2014
S3
Meaning
SIMOTION D410 does not run a user program.
● The technology packages are active. Test and commissioning functions can be
executed. The user program is not active.
● The I/O modules are in a secure state, i.e. the digital outputs have the status "LOW"
and the analog outputs are at zero current/voltage.
SIMOTION D410 does not run a user program.
● It is possible to load a complete user program.
● All system services (communications, etc.) are active.
● The I/O modules are in a secure state, i.e. the digital outputs have the status "LOW"
and the analog outputs are at zero current/voltage.
● The technology packages are inactive, i.e., all enables are deleted. No axis motions
can be executed.
0
Module memory reset/restoring D410 to factory settings
Regardless of the operating sequence, you can use the MRES switch setting to
- reset the SIMOTION D410 memory or
- restore the SIMOTION D410 to its factory settings.
With V4.1 SP2 and higher, MRES is only used if no service function has been selected
(i.e. switches S1 to S7 must remain OFF (0)).
For additional details on the operating sequence, refer to the
Commissioning Manual.