Operator Controls; Service And Operating Mode Switches - Siemens SIMOTION D410 Manual

Hide thumbs Also See for SIMOTION D410:
Table of Contents

Advertisement

Operation (hardware)

3.2 Operator controls

3.2
Operator controls
3.2.1

Service and operating mode switches

DIP switches
The SIMOTION D410 features operating mode and service selector switches at the bottom of
its front side (see Overview of operator controls and indicators (Page 35)). These function
using a DIP switch (DIP = Dual In Line Package), where:
● switches S1 to S3 set the operating mode and
● switches S4 to S7 select the service functions
During "normal" operation, the switch settings shown in the figure below must be retained.
Figure 3-2
DIP switches (factory setting)
The modes and service functions that can be set are outlined below.
Mode selector switches
The table shows the possible settings for the mode selector switches.
Table 3-1
Mode selector switch settings
Operating
S1
S2
mode
RUN
1
1
(three switches =
ON)
36
S3
Meaning
1
SIMOTION D410 runs the user program and all connected system performances:
● Read process image of inputs.
● Execution of the user programs assigned to the execution system.
● Write process image of outputs.
The technology packages are active in this state. They can execute commands from the
user program.
SIMOTION D410