Interfaces
4.4 PROFIBUS DP interface (SIMOTION D410 DP only)
SIMOTION D410 includes master and I-slave functionality.
Note
If a SIMOTION D410 DP is operated as a passive PROFIBUS I-slave, the display, measuring
functions, and controller optimization engineering functions will be very slow. If possible, use
the "active I-slave" setting for local commissioning (which does mean that an equidistance is
no longer possible) and for complete commissioning, switch to "passive I-slave".
Interface characteristics
Table 4-8
Characteristic
Connector type
Cable type
Maximum cable length
Maximum data rate
Interface assignment
Table 4-9
Interface assignment X21
Representation
Note
A teleservice adapter can be connected to the PROFIBUS interface (X21) for remote
diagnosis.
The power supply for the teleservice (terminals 2 and 7) can take up to 150 mA and is
sustained short-circuit proof.
50
Interface X21
Pin
Name
1
-
2
M24_SERV
3
RxD/TxD-P
4
CNTR-P
5
DGND
6
VP
7
P24_SERV
8
RxD/TxD-N
9
-
Type
9-pin SUB-D socket
PROFIBUS cable
100 m at 12 Mbit/s
12 Mbit/s
Description
unassigned
Teleservice supply, ground
Receive/transmit data P (B)
Control signal
PROFIBUS data reference potential
Supply voltage plus
Teleservice supply, + (24 V)
Receive/transmit data P (N)
unassigned
Area
0 V
RS485
TTL
5 V +/- 10 %
24 V (20.4 V - 28.8 V)
RS485