6.5 Connecting the protective ground

6.4

Overview of SIMOTION D410 connections

Figure 6-3
6.5
Connecting the protective ground
Connect SIMOTION D410 to the protective ground. An M4 protective ground screw is available
(see figure "Location of interfaces and front elements in SIMOTION D410" in Chapter
"Description").
The cross-section of the cable running to the protective ground must be at least 10 mm².
1. Remove the M4 protective ground screw.
2. Connect the protective ground and screw the protective ground screw back into the insert
74
Overview of connections
nut (Torx screwdriver, size 20).
WARNING
Danger to life from electric shock due to insufficient grounding
Ensure the connection to the protective ground is low resistance.
Provide a flexible cable to the protective conductor if SIMOTION D410 is mounted on a
movable frame.
SIMOTION D410
Manual, 04/2014