Operation (hardware)
3.2 Operator controls
Service selector switches (V4.1 SP2 and higher)
The table below shows the possible settings for the service selector switches. The service
functions are selected using switches S4 to S7 and may, in principle, be used in any operating
mode set (switch S1 to S3).
Table 3-2
Service selector switch settings
Service mode
Back up diagnostic
data and non-volatile
data
Delete/restore non-
volatile data
Downgrade
(device update tool)
Additional references
Detailed information
● For information on setting the operating modes, refer to the
● For information on updating devices (device update tool), refer to the
3.2.2

SIMOTION CompactFlash card

CompactFlash card slot
The CompactFlash card (CF card) is inserted into the plug-in module over the blanking plate
(see "Overview of operator controls and indicators").
Characteristics of the CF card
The CF card is mandatory for operation of SIMOTION D410. The CF card must be ordered as
a separate component; it is not included in the SIMOTION D410 scope of delivery.
The SIMOTION firmware is located on the CF card.
The licenses for the technology functions are linked to serial number of the CF card. This
means the CF card can be inserted in various SIMOTION D410s without having to change the
licenses.
38
S4
S5
S6
S7
0
0
0
1
0
1
0
0
0
0
1
0
Configuration Manual.
Devices Operating Instructions.
Meaning
The diagnostic data and non-volatile data can be backed up in STOP,
STOPU, and RUN mode. The advantage of backing up in RUN mode
is the availability of enhanced diagnostic functions (via websites) and
TO alarm information.
When the "Delete/restore non-volatile data" switch setting is selected,
the non-volatile data of the D410 is first deleted and then restored along
with the contents of the PMEMORY backup file.
SIMOTION D410 Control Units and projects can be updated using
update data created at an earlier point in time. This involves creating
update data using a device update tool ("Project > Start Device Update
Tool" menu in SIMOTION SCOUT).
If the result of the update is not what was desired, this switch setting
can be used to discard it and downgrade to the previous configuration.