Overview Of Simotion D410 Connections; Connecting The Protective Ground - Siemens SIMOTION D410 PN Manual

Hide thumbs Also See for SIMOTION D410 PN:
Table of Contents

Advertisement

Connecting

5.4 Overview of SIMOTION D410 connections

5.4
Overview of SIMOTION D410 connections
Figure 5-3
5.5

Connecting the protective ground

Connect SIMOTION D410 to the protective ground. An M4 protective ground screw is
available (see figure "Location of interfaces and front elements in SIMOTION D410" in
Chapter "Description").
The cross-section of the cable running to the protective ground must be at least 10 mm².
1. Remove the M4 protective ground screw.
2. Connect the protective ground and screw the protective ground screw back into the insert
66
Overview of connections
nut (Torx screwdriver, size 20).
CAUTION
Always ensure the connection to the protective ground is low resistance. If
SIMOTION D410 is mounted on a movable frame, you must provide a flexible cable to
the protective ground.
SIMOTION D410
Manual, 02/2012

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion d410 dpSimotion d410

Table of Contents