Connecting
5.3 Overview of SIMOTION D410 connections
5.3
Overview of SIMOTION D410 connections
Figure 5-1
5.4
Connecting the protective ground
Connect SIMOTION D410 to the protective ground. An M4 protective ground screw is
available (see figure "Location of interfaces and front elements in SIMOTION D410" in
Chapter "Description").
The cross-section of the cable running to the protective ground must be at least 10 mm².
1. Remove the M4 protective ground screw.
2. Connect the protective ground and screw the protective ground screw back into the insert
Caution
Always ensure the connection to the protective ground is low resistance. If SIMOTION D410
is mounted on a movable frame, you must provide a flexible cable to the protective ground.
50
Overview of connections
nut (Torx screwdriver, size 25).
D410
Manual, 03/2007 Edition