Technical Data; Start - Beckhoff EL3182 Documentation

2 channel analog input teminal (4...20 ma), single-ended, 16 bit, hart
Table of Contents

Advertisement

Product overview
2.2

Technical data

Technical data
Number of inputs
Technology
Signal type
Signal current
Power supply
Internal resistance
Input filter limit frequency
Dielectric strength
Measuring range, technical
Resolution
Measuring error
Distributed clocks
Electrical isolation
Current consumption power contacts
Current consumption E-bus
Bit width in the process image
Special features
Max. allowed output current (Uv1 / Uv2)
Weight
Permissible ambient temperature range during
operation
Permissible ambient temperature range during
storage
Relative humidity
Dimensions (W x H x D)
Mounting [} 26]
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Approval
2.3

Start

For commissioning:
• mount the EL3182 as described in the chapter Mounting and wiring [} 26]
• configure the EL3182 in TwinCAT as described in chapter Commissioning [} 42]
14
EL3182
2
HART Version 7
single-ended
4...20 mA
via the E-bus
typ. 250 Ω
25 Hz
max. 30 V
generally 107 % of the nominal measuring range
16 bit (incl. sign)
< ±0.3 % (relative to full scale value)
Yes
500 V (E-bus/signal voltage)
-
typ. 130 mA
8 byte, HART: 28 byte per channel as option
• Standard and compact process image
• Activatable FIR/IIR filters
• Limit value monitoring
• ExtendedRange 107 %
• NE43 NAMUR
typ. 150 mA (per connector)
approx. 60 g
-25°C ... + 60°C
-40°C ... + 85°C
95 %, no condensation
approx. 15 mm x 100 mm x 70 mm (width aligned: 12
mm)
on 35 mm mounting rail conforms to EN 60715
according to EN 60068-2-6/EN 60068-2-27,
see also installation instructions [} 29] for terminals
with increased mechanical load capacity
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE
Version: 1.2