5.1.1 DC Fuse/Breaker AMPS HP2: Rack Mount
Alpha recommends using fuses instead of breakers because they provide better fault protection.
NOTE:
The recommendations in Table B are for reference only. A registered professional
engineer must review and approve or modify these recommendations in compliance
with applicable national and local electrical and building codes.
Table B — Recommended DC fuse/breaker
DC
input
Recommended minimum 
DC fuse/breaker rating 
(100% rated, per feed)
0260080-J0 Rev D
Model
Maximum DC Input wattage
Maximum DC Input Current
@ 48 Vdc, full load
Single DC feed
Dual DC feed
27kW
18kW
555A
375A
700A
500A
350A
250A
9kW
188A
250A
125A