Table 80. Expanded operating temperature specifications (continued)
Expanded operating temperature
NOTE:
When operating in the expanded temperature range, the performance of the system may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported on the
System Event Log.

Expanded operating temperature restrictions

Thermal Restriction for ASHRAE A4 Environment (UI)
CPU TDP equal or greater than 155 W are not supported within A4.
128GB or greater capacity LRDIMMs are not supported within A4.
Redundant power supply configuration is required.
Non-Dell qualified peripheral cards greater than Tier 5 are not supported.
GPU card is not supported within A4.
OCP is not supported within A4.
H730/H740 Mini-PERC is not supported with A4.
PCIe SSD is not supported within A4.
Thermal Restriction for ASHRAE A3 Environment (UI)
CPU TDP equal or greater than 180 W are not supported within A3.
128GB or greater capacity LRDIMMs are not supported within A3.
Redundant power supply configuration is required.
Non-Dell qualified peripheral cards greater than 25 W are not supported.
GPU card is not supported within A3.
OCP is not supported within A3.
PCIe SSD is not supported within A3.
Particulate and gaseous contamination
specifications
The following table defines the limitations that help avoid any damages to the IT equipment and/or, or both failure from particulate and
gaseous contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and results in equipment damage or
failure, you must rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 81. Particulate contamination specifications
Particulate contamination
Air filtration
140
Technical specifications
Specifications
up to 45°C for a maximum of 1% of its annual operating
hours.
For temperatures 40°C– 45°C, derate maximum allowable
temperature by 1°C per 125 m (1°F per 228 ft) above 950 m (3.117
ft).
Specifications
Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit.
NOTE:
This condition applies to data center
environments only. Air filtration requirements do not
apply to IT equipment designed to be used outside a data
center, in environments such as an office or factory
floor.
NOTE:
Air entering the data center must have MERV11
or MERV13 filtration.