7.10.2

Safety monitor

The AS-i safety monitor reads the diagnosis data of the AS-i safety monitor and
shows on the display. The meaning of the shown diagnosis can be seen in the de-
scription of the safety monitor.
7.10.3

Safety Subst Value

With this function the input-data-substitution by safety slaves can be turn off/on.
SUBSTITUTE
The input-data are replaced mit following values:
Both channels released: 0000bin
Channel 1 released: 0011bin
Channel 2 released: 1100bin
No channel has released: 1111bin
NO SUBSTITUTE
The safety slave input data are shown unmodified.
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Operating in Advanced Display Mode
S A F E T Y M O N I T O R
D I A G N O S I S
A D D R :
1 7
M O D E :
S O R T E D / V 1
S TAT U S : O . K .
C H . 1 :
O F F
C H . 2 :
O F F
1 - 3 2 :
G R E E N
. . .
S A F E T Y S U B S T VA L
S U B S T I T U T E
C H A N G E
AS-i EtherNet/IP Gateway
Copyright Pepperl+Fuchs, Printed in Germany