Control Menu (Option); As-I Control; As-I Control Information; As-I Control Run - Pepperl+Fuchs VBG-EN-K20-D Manual

As-interface/ethernet ip-gateway
Hide thumbs Also See for VBG-EN-K20-D:
Table of Contents

Advertisement

7.3.1

Control menu (option)

7.3.1.1

AS-i control

7.3.1.2

AS-i control information

This function displays the current status of the AS-control (control program).
START BIT SET: the control program was started.
START BIT RESET: the control program was stopped.
RUNNING: the control program is running.
STOPPED: the control program was stopped.
The control program can be stopped even though the start bit was set. Example:
any configuration error occurs, or the master is in the configuration mode.
CYCLE TIME ACT: current cycle time of the control program.
CYCLE TIME MAX: maximal cycle time of the control program since its last start.
7.3.1.3

AS-i control run

CONTROL RUN: the control program can be stopped with this function. It modifies
the start bit in the menu Control Info.
RUN: the control program has been started. Even if the start bit is set, the control
program can be stopped; example: any cofiguration error occurs, or the master is
in the configuration mode.
CHANGE: the configuration program is stopped.
Subject to reasonable modifications due to technical advances.
34
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Operating in Advanced Display Mode
C O N T R O L
I N F O
C O N T R O L
R U N
C O N T R O L
F L A G S
C O N T R O L
I N F O
S TA R T B I T S E T
R U N N I N G
C Y C L E T I M E
A C T:
2 M S
M A X :
5 M S
C O N T R O L
R U N
R U N
C H A N G E
AS-Interface
Copyright Pepperl+Fuchs, Printed in Germany