The single slave configuration for the 16-bit module is written.
This command must be repeated for all 31 A-slaves and all 31 B-slaves. If you
don't connect a slave to an address, write F
3. Write new list of projected slaves
Write the complete LPS of your AS-i circuit.
Every bit in the LPS corresponds to one slave after the following scheme:
Byte0/Bit 0:slave 0/0A - can not be set!
Byte1/Bit 1:slave 1/1A
...
Byte3/Bit 7:slave 31/31A
Byte4/Bit 0:slave 0B - can not be set!
Byte4/Bit 1:slave 1B
...
Byte7/Bit 7:slave 31B
The slave is projected if the bit is set.
Example above: 16-bit module at address 4 ⇒ Set bit 4/byte 0:
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
...
Byte 11
Byte 12
Byte 1
Byte 2
...
Byte 12
No result because toggle bit = 0.
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Request: SET_LPS
29
(SET_LPS)
hex
00
(T = 0, master 1, single master)
hex
00
hex
10
(LDS byte 0)
hex
00
(LDS byte 1)
hex
...
00
(LDS byte 7)
hex
00
hex
Response
00
(or old values)
hex
00
(or old values)
hex
...
00
(or old values)
hex
AS-i EtherNet/IP Gateway
Command Interface
for ID, IO, ID1, ID2.
hex
Copyright Pepperl+Fuchs, Printed in Germany
117