Pepperl+Fuchs VBG-EN-K20-D Manual page 50

As-interface/ethernet ip-gateway
Hide thumbs Also See for VBG-EN-K20-D:
Table of Contents

Advertisement

Byte 2:
Bit 0:Config_OK
Bit 1:LDS.0
Bit 2:Auto_Addr_Asn
Bit 3:Auto_Addr_Avl
Bit 4:Config_Active
Bit 5:Normal_Op.
Bit 6:AS-i Pwr Fail
Bit 7:Offline_Ready
Byte 3:
Bit 0:Data_Exch_Act
Bit 1:Offline
Bit 2:Auto_Addr_Ena
Subject to reasonable modifications due to technical advances.
48
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Operating in Advanced Display Mode
The flag is set, if the projected configuration corresponds with the ac-
tual configuration.
The flag is set, if an AS-i slave with address 0 has been detected.
The flag is set, if the automatic addressing is possible
(AUTO_ADDR_ENABLE = 1; no "incorrect" AS-i slave is conntected to
AS-i).
The flag is set, if the automatic addressing is possible. This means that
exactly one slave is failed.
The flag is set in the configuration mode and is reset in the protected
mode.
The flag is set, if the AS-i master is in normal operation.
The flag is set, if the AS-i circuit is not sufficiently powered.
The flag is set, if the AS-i master is in the offline phase.
If the flag "Data Exchange Active" is set, the data exchange is released
with the AS-i slaves in the data exchange phase. If the bit is not set, the
data exchange with AS-i slaves will be locked. Instead of data tele-
gramms READ_ID telegramms will be sent.
The bit is set by the AS-i master by change over in the offline phase.
This bit is set if the operating mode offline is to be or already taken.
This flag indicates if the automatic addressing is locked (bit = 0) or re-
leased (bit = 1) by the user.