8.4

Functional profiles

8.4.1

"Safety at Work" List 1

This function has been implemented only for reasons of the downwards com-
patibility.
By AS-i 3.0 Masters, the state of the "safety input slaves" is specified on the
image of the input data (0000 released).
Function: 00
List of "safety-directed input slaves" ("AS-i Safety at Work"), whose safety function
is released.
Safety-directed input slaves have the profile S-7.B or S-0.B (IO = 0 or 7, ID = B,
see chapter 8.3.5.4: Read Actual Configuration).
The "Safety at Work" list 1 is a bit list which contains a bit for each possible slave
address (1 - 31). This list is written in the bytes 5 until 8 in the response of the com-
mand of the command interface. Additionally, the reponse contains the ec-flags
of the AS-i master in the bytes 3 and 4 (see chapter 8.3.4.3: "Get Flags").
The bits of the "Safety at Work" list 1 are set if the safety function of the slave is
activated (e.g. emergency button pressed). The bit is only set at security slaves
when both contacts are released, otherwise the bits have the value 0. "Normal"
(non-security) slaves also have the value 0.
Since the safety monitor is also being activated when a safety slave is missing or
if the AS-i circuit is shut off (offline active), the ec-flags will also be transmitted. It
is sufficient however to monitor the group error message Cok (configuration error).
As long as no configuration error, the list of the "safety-directed input slaves" can
be used.
Configured safety slaves which are not available, and available slaves sending a
wrong coder order, will not be entered in this list.
With the bit "O", the sequence of the bits within the "Safety at Work" list 1 can be
chosen.
Cok Config_Ok
S0
LDS.0
AAs Auto_Address_Assign
AAv Auto_Address_Available
CA
Configuration_Active
NA
Normal_Operation_Active
APF APF
OR Offline_Ready
Pok Periphery_Ok
Example for O ≡ 0:
Configuration OK,
periphery OK (no peripheral fault,
2 safety slaves with released safety function,
AS-Inferface addresses 4 and 10
Subject to reasonable modifications due to technical advances.
98
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
16
AS-Interface
Command Interface
Copyright Pepperl+Fuchs, Printed in Germany

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vbg-en-k20-md

Table of Contents