18 Troubleshooting
Code
Name
PGo
Encoder (PG) Feedback Loss
PGoH
Encoder (PG) Hardware Fault
rUn
Motor Switch during Run
SE
Modbus Test Mode Error
STo
Safe Torque OFF
SToF
Safe Torque OFF Hardware
TiM
Keypad Time Not Set
TrPC
IGBT Maintenance Time (90%)
UL3
Undertorque Detection 1
UL4
Undertorque Detection 2
UL5
Mechanical Weakening Detection 2
Uv
Undervoltage

Parameter Setting Errors

Parameter setting errors occur when multiple parameter settings do not agree, or when parameter setting values are
not correct. Refer to the table in this section, examine the parameter setting that caused the error, and remove the
cause of the error. You must first correct the parameter setting errors before you can operate the drive. The drive will
not send notification signals for the faults and alarms when these parameter setting errors occur.
Code
Name
oPE01
Drive Capacity Setting Error
oPE02
Parameter Range Setting Error
78
Causes
The main circuit capacitors have become
unserviceable.
The encoder cable is disconnected or wired
incorrectly.
The encoder cable is disconnected.
The drive received a Motor 2 Selection [H1-xx = 16]
during run.
MEMOBUS/Modbus communications self-
diagnostics [H1-xx = 67] was done while the drive
was running.
Safe Disable inputs H1-HC and H2-HC are open.
There is internal damage to the two Safe Disable
channels.
One of the two terminals H1-HC or H2-HC received
the Safe Disable input signal.
The Safe Disable input signal is wired incorrectly.
There is internal damage to one Safe Disable channel.
There is a battery in the keypad, but you have not set
the date and time.
The IGBT is at 90% of its expected performance life.
A fault occurred on the machine.
Example: There is a broken pulley belt.
A fault occurred on the machine.
Example: There is a broken pulley belt.
The drive detected undertorque as specified by the
conditions for mechanical weakening detection set in
L6-08 [Mechanical Fatigue Detect Select].
The drive input power voltage is changing too much.
Causes
The value set in o2-04 [Drive Model (KVA) Selection]
does not agree with the drive model.
Parameters settings are not in the applicable setting
range.
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
Possible Solutions
• Examine the capacitor maintenance time in monitor U4-05
[CapacitorMaintenance].
• If U4-05 is more than 90%, replace the capacitor. Contact
Yaskawa or your nearest sales representative for more
information.
• Examine the input power for problems.
• Re-energize the drive.
• If the alarm stays, replace the circuit board or the drive. Contact
Yaskawa or your nearest sales representative for more
information.
Examine for wiring errors or disconnected wires in the encoder
cable, and repair problems.
Correct any disconnected wires in the encoder cable.
Make sure that the drive receives the Motor 2 Selection while the
drive is stopped.
Stop the drive and do MEMOBUS/Modbus communications self-
diagnostics.
• Make sure that the Safe Disable signal is input from an external
source to terminal H1-HC and H2-HC.
• When the Safe Disable function is not in use, use a jumper to
connect terminals H1-HC and H2-HC.
Replace the board or the drive. Contact Yaskawa or your nearest
sales representative to replace the board.
• Make sure that the Safe Disable signal is input from an external
source to terminals H1-HC or H2-HC.
• When the Safe Disable function is not in use, use a jumper to
connect terminals H1-HC and H2-HC.
Replace the board or the drive. Contact Yaskawa or your nearest
sales representative to replace the board.
Use the keypad to set the date and time.
Replace the IGBT or the drive. For more information, contact
Yaskawa or your nearest sales representative.
Examine the machine and remove the cause of the fault.
Examine the machine and remove the cause of the fault.
Examine the machine for deterioration.
• Examine the input power for problems.
• Make the drive input power stable.
• If the input power supply is good, examine the magnetic
contactor on the main circuit side for problems.
Possible Solutions
Set o2-04 to the correct value.
1.
Push
to show U1-18 [oPE Fault Parameter], and find
parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other oPExx
errors have priority over oPE02.