YASKAWA GA800 600 V Drive Installation & Primary Operation page 51

For industrial applications
Table of Contents

Advertisement

No.
(Hex.)
E1-06
Base Frequency
(0305)
E1-09
Minimum Output Frequency
(0308)
E2-01
Motor Rated Current (FLA)
(030E)
E2-11
Motor Rated Power
(0318)
H1-01 - H1-08
Terminal S1 to S8 Function
Selection
(0438, 0439, 0400 -
0405)
H2-01
Term M1-M2 Function Selection
(040B)
H2-02
Term M3-M4 Function Selection
(040C)
H2-03
Term M5-M6 Function Selection
(040D)
H3-01
Terminal A1 Signal Level Select
(0410)
H3-02
Terminal A1 Function Selection
(0434)
H3-03
Terminal A1 Gain Setting
(0411)
RUN
H3-04
Terminal A1 Bias Setting
(0412)
RUN
H3-05
Terminal A3 Signal Level Select
(0413)
H3-06
Terminal A3 Function Selection
(0414)
H3-07
Terminal A3 Gain Setting
(0415)
RUN
H3-08
Terminal A3 Bias Setting
(0416)
RUN
H3-09
Terminal A2 Signal Level Select
(0417)
H3-10
Terminal A2 Function Selection
(0418)
H3-11
Terminal A2 Gain Setting
(0419)
RUN
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
Name
V/f
CL-V/f
Sets the base frequency for the V/f pattern.
V/f
CL-V/f
Sets the minimum output frequency for the V/f pattern.
V/f
CL-V/f
Sets the motor rated current in amps.
V/f
CL-V/f
Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].
V/f
CL-V/f
Sets the functions for MFDI terminals S1 to S8.
V/f
CL-V/f
Sets the function for MFDO terminal M1-M2.
V/f
CL-V/f
Sets the function for MFDO terminal M3-M4.
V/f
CL-V/f
Sets the function for MFDO terminal M5-M6.
V/f
CL-V/f
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
CL-V/f
Sets the function for MFAI terminal A1.
V/f
CL-V/f
Sets the gain of the analog signal input to MFAI terminal A1.
V/f
CL-V/f
Sets the bias of the analog signal input to MFAI terminal A1.
V/f
CL-V/f
Sets the input signal level for MFAI terminal A3.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
CL-V/f
Sets the function for MFAI terminal A3.
V/f
CL-V/f
Sets the gain of the analog signal input to MFAI terminal A3.
V/f
CL-V/f
Sets the bias of the analog signal input to MFAI terminal A3.
V/f
CL-V/f
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
V/f
CL-V/f
Sets the function for MFAI terminal A2.
V/f
CL-V/f
Sets the gain of the analog signal input to MFAI terminal A2.
11 Drive Control, Duty Modes, and Programming
Description
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
OLV
CLV
AOLV
51