L1-03: Motor Thermistor Oh Alarm Select; L1-04: Motor Thermistor Oh Fault Select - YASKAWA GA800 600 V Drive Installation & Primary Operation

For industrial applications
Table of Contents

Advertisement

Shows the motor protection operation time characteristics when overload occurs from continuous operation below
the motor rated current.
Figure 12.3 Protection Operation Time for a General-purpose Motor at Rated Output Frequency

L1-03: Motor Thermistor oH Alarm Select

No.
Name
(Hex.)
L1-03
Motor Thermistor oH Alarm
Select
(0482)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON and MB-
MC turns OFF.
1 : Coast to Stop
The output turns OFF and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows oH3, and operation continues. The output terminal set for Alarm [H2-01 to H2-03 = 10] turns ON.

L1-04: Motor Thermistor oH Fault Select

No.
Name
(Hex.)
L1-04
Motor Thermistor oH Fault
Select
(0483)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON and MB-
MC turns OFF.
1 : Coast to Stop
The output turns OFF and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
V/f
CL-V/f
OLV
CLV
AOLV
Sets drive operation when the PTC input signal entered into the drive is at the oH3 [Motor Overheat
Alarm] detection level.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive operation when the PTC input signal to the drive is at the oH4 [Motor Overheat Fault
(PTC Input)] detection level.
Description
Description
12 UL Standards
Default
(Range)
3
(0 - 3)
Default
(Range)
1
(0 - 2)
59