8 Keypad: Names and Functions
No.
Name
RUN LED
A
ALM LED
B
microSD Card Insertion Slot The insertion point for a microSD card.
C
Function Keys
(F1, F2, F3)
D
LO/RE LED
E
LO/RE Selection Key
F
STOP Key
G
Left Arrow Key
Up Arrow Key/Down Arrow
Key
/
H
Right Arrow Key (RESET)
ENTER Key
RUN Key
I
J
USB Terminal
K
RJ-45 Connector
28
Table 8.1 Keypad: Names and Functions
Illuminates to show that the drive is operating the motor.
The LED turns OFF when the drive stops.
Flashes to show that:
• The drive is decelerating to stop.
• The drive received a Run command but the frequency reference is 0 Hz.
Flashes quickly to show that:
• The drive received a Run command from the Multi-Function Digital Input (MFDI) terminals and is switching to REMOTE Mode while
the drive is in LOCAL Mode.
• The drive received a Run command from the MFDI terminals when the drive is not in Drive Mode.
• The drive received a Fast Stop command.
• The safety function shuts off the drive output.
• The user pushed
on the keypad while the drive is operating in REMOTE Mode.
• The drive is energized with an active Run command and b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command].
Illuminates when the drive detects a fault.
Flashes when the drive detects:
• Alarm
• An oPE parameter setting error
• A fault or alarm during Auto-Tuning
The light switches off when the drive is in normal operation. There is no fault or alarm.
The menu shown on the keypad sets the functions for function keys.
The name of each function is in the lower half of the display window.
Illuminated: The keypad controls the Run command (LOCAL Mode).
OFF: The control circuit terminal or serial transmission device controls the Run command (REMOTE Mode).
Note:
• LOCAL: Operated using the keypad. Use the keypad to enter Run/Stop commands and the frequency reference command.
• REMOTE: Operated from the control circuit terminal or serial transmission. Use the frequency reference source entered in b1-01 and
the Run command source selected in b1-02.
Switches drive control for the Run command and frequency reference between the keypad (LOCAL) and an external source (REMOTE).
Note:
• Stop operation to enable the LO/RE Selection Key when in Drive Mode. Set o2-01 = 0 [LO/RE Key Function Selection = Disabled] to
disable
when switching from REMOTE to LOCAL will have a negative effect on system performance.
• The drive will not switch between LOCAL and REMOTE when it is receiving a Run command from an external source.
Stops drive operation.
Note:
The STOP key has highest priority. Push
external Run command source. Set o2-02 = 0 [STOP Key Function Selection = Disabled] to disable the priority in
Moves the cursor to the left.
• Scrolls up or down to display the next item or the previous item.
• Selects parameter numbers, and increments or decrements setting values.
• Moves the cursor to the right.
• Continues to the next screen.
• Clears drive faults.
• Enters parameter values and settings.
• Selects menu items to move the user between keypad displays.
• Selects each mode, parameter, and set value.
Starts the drive in LOCAL mode.
Starts the motor tuning procedure in Auto-Tuning Mode.
Note:
Push
on the keypad to set the drive to LOCAL Mode before using the keypad to operate the motor.
Insertion point for a mini USB cable. Uses a USB cable (USB standard 2.0, type A - mini-B) to connect the keypad to a PC.
Connects to the drive using an RJ-45 8-pin straight through UTP CAT5e extension cable or keypad connector.
Function
to stop the motor even when a Run command (REMOTE Mode) is active at any
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
.