YASKAWA GA800 600 V Drive Installation & Primary Operation page 73

For industrial applications
Table of Contents

Advertisement

Code
Name
PE1, PE2
PLC Faults
PF
Input Phase Loss
PGo
Encoder (PG) Feedback Loss
PGoH
Encoder (PG) Hardware Fault
rF
Braking Resistor Fault
rH
Braking Resistor Overheat
rr
Dynamic Braking Transistor Fault
SC
Short Circuit/IGBT Failure
SCF
Safety Circuit Fault
SEr
Speed Search Retries Exceeded
SvE
Zero Servo Fault
TiM
Keypad Time Not Set
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
Causes
The load inertia is set incorrectly.
There is motor hunting.
The communication option detected a fault.
There is a phase loss in the drive input power.
There is loose wiring in the drive input power
terminals.
The drive input power voltage is changing too much.
There is unsatisfactory balance between voltage
phases.
The main circuit capacitors have become
unserviceable.
The encoder cable is disconnected or wired
incorrectly.
The encoder cable is disconnected.
The resistance of the dynamic braking option that is
connected to the drive is too low.
The deceleration time is too short and excessive
regenerative energy is flowing back into the drive.
The duty cycle is too high.
The braking load is too large.
The braking resistor is not sufficient.
There is damage to the drive control circuit.
There is a malfunction in the internal braking
transistor of the drive.
Overheating caused damage to the motor or the motor
insulation is not satisfactory.
The safety circuit is broken.
The speed search-related parameters are set
incorrectly.
The value set in the torque limit is too small.
There is a battery in the keypad, but the date and time
are not set.
18 Troubleshooting
Possible Solutions
• Examine the load inertia settings with KEB, overvoltage
suppression, or stall prevention during deceleration.
• Adjust L3-25 [Load Inertia Ratio] to align with the qualities of
the machine.
• Adjust n1-02 [Hunting Prevention Gain Setting] settings.
• Adjust n2-02 [Automatic Freq Regulator Time 1] and n2-03
[Automatic Freq Regulator Time 2] settings.
Refer to the manual for the communication option card.
Correct errors with the wiring for main circuit drive input power.
Tighten the terminal screws to the correct tightening torque.
• Examine the input power for problems.
• Make the drive input power stable.
• If the input power supply is good, examine the magnetic
contactor on the main circuit side for problems.
• Examine the input power for problems.
• Make the drive input power stable.
• Set L8-05 = 0 [Input Phase Loss Protection Sel = Disabled].
• Examine the capacitor maintenance time in monitor U4-05
[CapacitorMaintenance]. If U4-05 is more than 90%, replace the
control board or the drive. For information about replacing the
control board, contact Yaskawa or your nearest sales
representative.
• If drive input power is correct and the fault stays, replace the
control board or the drive. For information about replacing the
control board, contact Yaskawa or your nearest sales
representative.
Examine for wiring errors or disconnected wires in the encoder
cable, and repair problems.
Connect any disconnected wires in the encoder cable.
Use a dynamic braking option that fits the model and duty rating of
the drive.
• Check the load level, deceleration time, and speed.
• Decrease the load.
• Increase the value set in C1-02, C1-04, C1-06, or C1-08
[Deceleration Times].
• Use a dynamic braking option that lets you use more power.
Examine the duty cycle.
Note:
When L8-01 = 1 [3% ERF DB Resistor Protection = Enabled],
the maximum braking duty cycle is 3%.
• Calculate the braking load and braking power again, and
decrease the braking load.
• Use a braking resistor that improves braking power.
Use the braking resistor specifications to select a sufficient braking
resistor.
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Measure the motor insulation resistance, and replace the motor if
there is electrical conduction or unserviceable insulation.
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest sales
representative.
• Decrease the value set in b3-10 [Speed Estimation Detection
Gain].
• Increase the value set in b3-17 [Speed Est Retry Current Level].
• Increase the value set in b3-18 [Speed Est Retry Detection Time].
• Do Auto-Tuning again.
Adjust torque limit-related parameters L7-01 to L7-04.
Use the keypad to set the date and time.
73

Advertisement

Table of Contents
loading

Table of Contents