Code
Name
Er-16
Inertia ID Error
Er-17
Reverse Prohibited Error

Backup Function Operating Mode Display and Errors

Operating Mode Display
When the drive does backup function tasks with the LCD keypad, the keypad will show the current task. These
indicators do not show that an error has occurred.
Keypad Display
Drive and Keypad mismatch.
Should the parameters be
restored?
Restore Restore from keypad
End
Backup Backup from Drive
Verify Keypad & Drive
Backup Function Runtime Errors
When an error occurs, the keypad shows a code to identify the error.
The table in this section shows the error codes. Refer to this table to remove the cause of the errors.
Note:
Push any key on the keypad to clear an error.
Code
Name
CPEr
Control Mode Mismatch
CPyE
Error Writing Data
CSEr
Control Mode Mismatch
dFPS
Drive Model Mismatch
iFEr
Keypad Communication Error
ndAT
Error Received Data
PWEr
DWEZ Password Mismatch
rdEr
Error Reading Data
82
Causes
The inertia found by the drive was too small or too
large during Inertia Tuning (10% or less, or 50000%
or more).
b1-04 = 1 [Reverse Operation Selection = Reverse
disabled] is set.
Note:
You cannot do Inertia Tuning if the drive cannot
rotate the motor in reverse.
Name
Detection of inconsistency between the
drive and keypad
Restoring parameters
Backup/restore/verify operation ended
normally
Backing up parameters
Verifying parameters
Causes
The keypad setting and drive setting for A1-02
[Control Method Selection] do not align.
Parameter restore did not end correctly.
The keypad is broken.
You tried to restore parameters to a drive model that
is different than the drive model you backed up.
There was a communications error between the
keypad and the drive.
The parameter settings for model and specifications
(power supply voltage and capacity) are different
between the keypad and the drive.
The parameters are not stored in the keypad.
The password set in the backup operation with qx-xx
[DriveWorksEZ Parameters] and rx-xx
[DriveWorksEZ Connections] is incorrect.
You tried to back up when o3-02 = 0 [Copy Allowed
Selection = Disabled].
• Decrease the values set for the frequency and amplitude of the
test signals used when doing inertia tuning. First, decrease the
test signal amplitude, and then do Inertia Tuning. If the error
continues, decrease the test signal frequency and do Inertia
Tuning again
• Correctly set the motor inertia as specified by the motor, and do
Inertia Tuning again.
1.
Enable reverse in the target machine.
2.
Set b1-04 = 0 [Reverse enabled].
3.
Do Inertia Tuning again.
Display
Normally displayed
Flashing
Normally displayed
Flashing
Flashing
1.
Set A1-02 on the drive to the same value that is on the keypad.
2.
Restore the parameters.
Restore the parameters.
Replace the keypad.
1.
Examine the drive model that you used to back up the
parameters.
2.
Restore the parameters.
Examine the connector or cable connection.
1.
Make sure that drive model and the value set in o2-04 [Drive
Model (KVA) Selection] align.
2.
Restore the parameters.
1.
Connect a keypad that has the correct parameters.
2.
Restore the parameters.
Set the DWEZ PC software password supplied by Yaskawa for the
DWEZ program user ID downloaded to the drive.
Set o3-02 = 1 [Enabled] and back up again.
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
Possible Solutions
State
The drive detected the connection of a
keypad from a different drive. Select [Yes]
to copy parameters backed up in the keypad
to the connected drive.
The parameters stored in the keypad have
been restored to the drive.
The parameter backup, restore, or verify
operation ended normally.
The parameters stored in the drive are being
backed up to the keypad.
The parameter settings stored in the keypad
and the parameter settings in the drive align
or are being compared.