Siemens Sinamics S120 Comissioning Manual page 161

With startdrive
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

4. Click in the "Comment" column and enter a comment for the signal.
Initially the parameter name is shown after inserting a parameter. This can be changed.
5. Repeat the procedure from step 1 until all of the signals to be recorded have been
entered into the table.
You can configure a maximum of 8 signals for each trace.
Configuring recording conditions
Select the required trigger condition in the "trigger mode" field in the drop-down list.
Figure 5-6
Configuring the recording conditions depends on the selected trigger condition:
Trigger condition: Start recording immediately
1. Enter the recording time under "Recording duration". The possible total duration is
displayed to the right.
Activate the option "Recording duration = max. recording duration" if you wish to set the
total duration.
2. Enter a recording cycle under "Cycle" The possible cycle settings depend on the number
of signals.
Commissioning with Startdrive
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
Configuring trace recording conditions
Diagnostics
5.3 Diagnostics via Startdrive
161