IP addresses in the project
A CU320-2 PN is created with the following IP addresses in a project in TIA Portal:
● Ethernet commissioning interface X127:
The addresses correspond to the addresses that have already been assigned in the
drive.
– IP address: 169.254.11.22
– Subnet mask: 255.255.0.0
● PROFINET interface X150:
The following addresses are assigned for X150:
– IP address: 192.168.0.1 (example)
– Subnet mask: 255.255.255.0
PROFINET addresses lie in the area of the PROFINET subnet of a SIMATIC S7 PLC
control, so that you can network the drive with a control system without having to adapt the
subnet mask and IP address.
Figure 4-30
Commissioning with Startdrive
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
CU320-2 PN interfaces
4.4 Establishing an online connection to the drive
Commissioning