Wiring Inputs And Outputs; Wiring A Duct Air Temperature Sensor To An Input - Carrier VVT Bypass Installation And Startup Manual

Hide thumbs Also See for VVT Bypass:
Table of Contents

Advertisement

Wiring inputs and outputs

WARNING Disconnect electrical power to the VVT Bypass Controller before wiring it. Failure to follow
this warning could cause electrical shock, personal injury, or damage to the controller.
CAUTION
Do not run sensor or relay wires in the same conduit or raceway with Class 1 AC or DC service wiring.
Do not abrade, cut, or nick the outer jacket of the cable.
Do not pull or draw cable with a force that may harm the physical or electrical properties.
Avoid splices in any control wiring.

Wiring a Duct Air Temperature sensor to an input

Part #33ZCSENDAT
The VVT Bypass Controller must be connected to a Duct Air Temperature (DAT) sensor that monitors the
temperature of the air delivered by the air source.
NOTE This document gives instructions for wiring the sensor to the VVT Bypass Controller. For mounting and
wiring the sensor, see the Carrier Sensors Installation Guide.
Wiring specifications
Cable from sensor to controller:
Maximum length:
VVT Bypass Controller
Installation and Start-up Guide
If <100 ft (30.5 meters)
If >100 ft (30.5 meters)
500 feet (152 meters)
Carrier Proprietary and Confidential
12
22 AWG, unshielded
22 AWG, shielded
CARRIER CORPORATION ©2017
All rights reserved