5 Installation Procedure

Procedure C

This section shows the procedure to install and wire the option on an HV600 drive.
Prepare the Drive for the Option
Before you install the option on a YASKAWA AC Drive HV600, make sure that the option software version is
PRG: 4400 or later.
Correctly wire the drive as specified by the manual packaged with the drive. Make sure that the drive functions
correctly. For information about drive connection and wiring, refer to the manuals for the drive on which you will
use this option.
A - Drive grounding terminal (FE)
B - Option
C - Included screws
D - Ground screw
E - Drive front cover
F - Keypad
Install the Option
Use this procedure to install the option.
DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before
servicing, disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal
capacitor stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage
decreases below 50 Vdc. When all indicators are OFF, measure for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
1.
Remove the keypad (B) and front cover (A).
Shut off power to the drive and wait for the time specified on the drive warning label at a minimum. Make
sure that the charge indicator LED is unlit, then remove the keypad and front cover. Refer to the drive
manuals for more information.
NOTICE
the option. Failure to obey can cause ESD damage to the option circuitry.
20
Figure 5.14 Drive Components with Option
Damage to Equipment. Observe correct electrostatic discharge (ESD) procedures when touching
G - LED label
H - Ground wire
I - Option modular connector CN1 port 1 (RJ45)
J - Option modular connector CN1 port 2 (RJ45)
K - Insertion point for CN5 connector
L - Connector CN5
YASKAWA SIEP C730600 89E PROFINET Technical Manual