8 Communication

Yaskawa Vendor-Specific Control and Status Words

The Control Word and the Status Word

The contents of the Control Word and the Status Word are detailed in

Frequency Reference

Frequency Reference is a 16-bit word containing the desired output frequency.

Output Frequency

Output Frequency is a 16-bit word containing the current output frequency of the drive.
Yaskawa-Specific Control Word
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
*1
Bit 11 is not used for GA500.
8
Communication
This section describes the PROFINET IO messaging used in communication with the drive.
For detailed information on PROFINET IO communication, refer to PROFINET specification Application Layer
protocol for decentralized periphery and distributed automation v2.0 available at www.profibus.com.

Introduction to PROFINET IO

PROFINET IO is a fieldbus protocol that enables communication between programmable controllers and
distributed field devices in Ethernet network. The protocol classifies devices into IO controllers, IO supervisors
and IO devices, which have a specific collection of services.
PROFINET IO uses three different communication channels to exchange data. The standard UDP/IP and TCP/IP
channel is used for parameterization and configuration of devices and for acyclic operations. The Real Time (RT)
channel is used for cyclic data transfer and alarms. The third channel, Isochronous Real Time (IRT) channel, is
used e.g. in motion control applications (not implemented in SI-EP3).
PROFINET IO devices are structured in slots and sub-slots, which can contain modules and sub-modules
correspondingly. Devices can have almost any number of slots and sub-slots and they can be virtual or real.
Device specific data is represented in slot 0, module and sub-module specific data in subsequent slots and sub-
slots.
32
Table 7.3 Yaskawa-Specific Control Word and Status Word
Description
Run bit
Reverse run bit
EF0
Fault Reset
DI1
DI2
DI3
DI4
DI5
DI6
DI7
*1
DI8
Not Used
Not Used
Not Used
Not Used
Table
7.3.
Yaskawa-Specific Status Word
Bit
0
1
2
Reverse Operation
3
Reset Signal Input Active
4
5
6
7
8
9
10
11
12
13
14
15
YASKAWA SIEP C730600 89E PROFINET Technical Manual
Description
Running
Zero Speed
At Speed
Ready
Alarm
Fault
oPE Fault
Uv Return
2nd Motor
ZSV
Not Used
Not Used
Net Reference
Net Control