Function
2.4.3

I/O Diagnostics Interface

The system CPX-E provides an I/O diagnostic interface in the form of 16 input bits and 16 output bits
for reading detailed diagnostic information. The I/O diagnostic interface can be used, for example, to
precisely determine the module and channel on which an error has occurred. In order to make use of
the I/O diagnostic interface, the bus module of the system CPX-E must be configured accordingly.
The I/O diagnostic interface is shown in the process image if this has been specified by selecting the
catalogue entry „E-PN [STI]" in the hardware configurator.
You can find detailed information about the I/O diagnostic interface in the "Description of system CPX-
E" è 1.1 Applicable Documents.
2.5

Diagnostics via PROFINET IO

The system CPX-E supports diagnostics options via PROFINET IO in accordance with IEC 61158; for
example, module-related and channel-related status information as well as error detection in the
online mode of the control software and in the PLC user program.
2.5.1

Error Numbers

With the exception of the CPX-E error numbers listed in è Tab. 12, the CPX-E error numbers in the
PROFINET IO network are transferred with an offset of 1000:
è CPX-E error number+ + 1000 =PROFINET IO error number
Error number
CPX-E
PROFINET IO
2
1
3
6
4
2
5
9
8
10
7
11
1
13
6
65
64
69
72
75
5
254
2
Tab. 12
14
Meaning
Short circuit
Wire break
Undervoltage
Lower critical limit undershot
Upper critical limit exceeded
Short circuit at valve
Wire break at valve
PROFIsafe addresses (F_Dest_Add) different
Parameterisation error (error in "safe parameterisation")
Excessive temperature
Undervoltage of electronics and sensors