Settings At The Logic Module - oventrop R-Tronic RT B Installation And Operating Instructions Manual

Table of Contents

Advertisement

Installation & initial operation
"R-Tronic" + "R-Con"

4.7.2 Settings at the logic module

With the logic module, the wireless receiver "R-Con" features an application
which contributes to the energy efficiency of the complete system by a target-
ed control of the heating pump.
Pump logic
The pump logic serves the adaptation of the heating pump or heating circuit
operation to the sluggish reaction of the thermal actuators. This is done by
defining a temporal switch-on delay (AV) and switch-off delay (RV) for
the pump.
As for the switch-on delay, the pump will only be switched on with a delay
after a heat demand for at least one channel (heating circuit) has been sig-
nalised by the "R-Tronic". As for the switch-off delay, the residual heat will
be pumped into the heating circuits for a certain time, even if actuators have
been switched off.
Exemplary switching sequence at the output of the pump logic after the
opening and closing process of an actuator:
(Illustration 43)
50

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R-tronic rtf bR-tronic rtfc k

Table of Contents