Installation & initial operation
PWM example 2
A lower parameter setting leads
to a stronger response behaviour
The lower the parameter value, the faster a room is heated to the nominal tem-
perature. So-called overshoots (slight overheating above the nominal value)
may, however, be caused by the longer "heating boosts".
PWM example 3
A higher parameter setting leads to a
weaker response behaviour
The higher the parameter value, the slower a room is heated to the nominal
temperature. Tendency to the so-called overshoots decreases. It is, however,
possible that the set nominal value is not reached.
48
"R-Tronic" + "R-Con"
(Illustration 39)
Nominal temperature: 22°C
Actual temperature:
Control deviation:
PWM parameter:
(Illustration 40)
Nominal temperature: 22°C
Actual temperature:
Control deviation:
PWM parameter:
21°C
1 K
1.5
21°C
1 K
3.0