Installation & initial operation
Burner logic
The burner logic serves to prevent wearing of the burner nozzle caused by
repeatedly switching the burner on and off for each individual heating circuit
and channel of the wireless receiver. A follow-up time of up to 15 minutes can
be set for this purpose. The burner does not need to be switched on again in
case of heat demands on other channels.
Determine the follow-up time of the burner with the help of the lower rota-
ry switch. If the burner logic is active, the LED embedded in the rotary
switch will glow green continuously.
Once the follow-up time has expired, the burner relay will be switched off
without delay as soon as the wireless receiver sends the signal to close the
actuator of a "teached in" channel. The burner relay has to be restarted for
each new heat demand.
52
NOTICE
Danger of damage to property!
It depends on the burner model whether
a switch-off delay (follow-up time) can be
activated. This has to be checked carefully.
If the selected switch-off delay is too long,
the temperature in the boiler may increase
and the safety shutdown of the boiler will
be triggered, if necessary.
"R-Tronic" + "R-Con"
(Illustration 45)