DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
11
Maintenance and Service
11.1
General Information
11.2
Replacing the Field Bus Coupler
11.2.1
General Information
11.2.2
Disconnecting the Cabling
11.2.3
Removing Field Bus Coupler from System
11.2.4
Removing Field Bus Coupler from Carrier Plate
This section contains information on maintenance and service.
To replace the field bus coupler in the event of version change, etc., proceed
as described in the following chapters.
Before removing the connector, clean the field bus coupler that no dirt comes
in contact with the connections. This could damage the contacts.
To unplug the cables, proceed as follows:
1. Disconnect the power supply from those devices on which the field bus
coupler has been mounted.
CAUTION
Even when taking into account derating, high surface temperatures on
the metallic connection sockets and on the enclosure can arise during
operation. If the IndraControl S67 component has been in operation, al‐
low it to cool off before touching it.
2. Unscrew all screw connections and remove the cables.
To remove the field bus coupler from the framework of the system, proceed
as follows:
1. Disconnect the power supply from those devices on which the field bus
coupler has been mounted.
2. Release the field bus coupler from the framework of the system by un‐
screwing the M4 screws.
In order to maintain clear representation, the carrier rail adapter in the figure
below (B, C) is shown without the field bus coupler.
If the field bus coupler is mounted on a carrier rail, proceed with the removal
as follows:
1. Disconnect the power supply from those devices on which the field bus
coupler has been mounted.
2. To remove the field bus coupler, press down the release eyebolt of the
carrier rail adapter using a slot screwdriver (B) and remove the carrier
rail adapter from the rail (C).
Bosch Rexroth AG
Maintenance and Service
Hot connection sockets!
121/139