DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
10
Diagnostics
10.1
LED Signaling
10.2
Ethernet Status Messages
The field bus coupler has various LEDs for local diagnostics that display its
operating state and that of the S-BUS.
The following table lists the Ethernet status messages that are signaled by
the LEDs (21) on the field bus coupler. Causes and remedies/information are
specified additionally.
21
Fig. 10-1:
LEDs to display Ethernet status messages
LED
Color/status
MS
Off
Green
Flashing green The Ethernet interface
Flashing red
ACT/LNK 1
Off
Green
Flashing green Data exchanged via
ACT/LNK 2
Off
Green
Flashing green Data exchanged via
Tab. 10-1:
Ethernet status messages
Bosch Rexroth AG
sercos
S3-BK-DI8
SBM
1 FB 2
1
FB 2
F
X
MS 1
CS
7
8
S3
NS
2
ACT/LNK
Cause
Remedy/information
No power supply ap‐
Check the power supply
plied at the field bus
for the field coupler.
coupler
Check the cable for
damage
The field bus coupler
–
operates correctly
Configure the field bus
of the field bus coupler
coupler (e.g. assigning
is not yet completely
an IP address)
configured
The Ethernet interface
The malfunction can be
could not be configured
recovered. Contact the
Bosch Rexroth Service
Field bus coupler has
Check the cable con‐
no connection to the
nection of the Ethernet
physical network
connection FB1
Connection to physical
–
network present
–
Ethernet
Field bus coupler has
Check the cable con‐
no connection to the
nection of the Ethernet
physical network
connection FB2
Connection to physical
–
network present
–
Ethernet
105/139