Bosch Rexroth IndraControl S67-S3-BK-DI8-M8 Application Description page 113

Sercos coupler 8 digital inputs (m8)
Table of Contents

Advertisement

DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
Group number
Designation
1
S-BUS error
2
S-BUS warnings
3
4
5
General internal hardware errors
6
General internal hardware warnings
7
General software errors
8
General software warnings
9
Specific, internal hardware errors
10
11
Field bus-specific software errors
12
Special software warnings
13
Firmware loader error
14
Error with firmware download
Tab. 10-4:
List of error groups
If the following errors and warnings cannot be remedied using the measures
indicated, then contact Bosch Rexroth Service (see
support" on page
133). Advise Bosch Rexroth of the corresponding blink
code that is displayed.
Error code Error argu‐
Cause
ment
1
0 ... 65
Error during S-BUS initiali‐
zation.
2
3
4
5
Error during S-BUS initiali‐
zation. The last I/O module
could not be initialized
Bosch Rexroth AG
111/139
Diagnostics
Display
CS LED
chapter 13 "Service and
Troubleshooting
Check the cable for dam‐
age.
Perform a restart by discon‐
necting the power supply
and then reconnecting it.
Check the cabling to and
from the last I/O module.
Ensure that the S-BUS ter‐
minator is inserted into the
last I/O module and no lon‐
ger connected to the field
bus coupler as 64 I/O mod‐
ules.

Hide quick links: