DOK-CONTRL-S67S3BKDI8*-AP03-EN-P
Rexroth IndraControl S67 Sercos Coupler 8 Digital Inputs (M8)
8.7

"Sercos Diagnostics" Page

8.8

"Sercos Timing" Page

This page provides diagnostic information on the Sercos field bus coupler.
Fig. 8-6:
"Sercos Diagnostics" page
The following table explains the information listed on the page:
Diagnostics
Description
Diagnostic message
Displays the Sercos-specific diagnostic message. The
content corresponds to parameter IDN/S-0-0095 "Diag‐
nostic message" of the Sercos specification
Diagnostic number
Displays the Sercos-specific diagnostic number. The con‐
tent corresponds to parameter IDN/S-0-0390 "Diagnostic
number" of the Sercos specification
Error counter port 1
Displays the number of the telegrams incorrectly received
on port 1
Error counter port 2
Displays the number of the telegrams incorrectly received
on port 2
Error counter MST-P/S
Displays the number of incorrectly received MST tele‐
grams. The content corresponds to parameter IDN/
S-0-1028 "Error counter MST-P/S" of the Sercos specifica‐
tion
IO Diagnosis message
Displays the Sercos-specific diagnostic message. The
content corresponds to parameter IDN/S-0-1500.0.32 "IO
Diagnostic Message" of the Sercos specification
Tab. 8-6:
Describing parameters of the "Sercos Diagnostics" page
This page provides information on the time behavior of the Sercos field bus
coupler.