Priva Compass Installation Manual page 92

Table of Contents

Advertisement

Priva
Analogue inputs
Input voltage range
Minimum input voltage for pulse control
Protection
Maximum length of input cable
Minimum core cross section
Digital inputs
Input voltage range
Protection
Maximum length of input cable
Minimum core cross section
Housing
IP code
Flammability class
Colour
Type of device
Installation and connection
Installation
Type of DIN rail
Environment
Permitted temperature inside control panel of a
working system
Permitted temperature during transport and
storage
Permitted ambient relative humidity
Shock and vibration resistance
Installation category
Legislation and standards
Europe
90
0 ... 10 VDC
2 V
input protected against overvoltage up to 30 VDC and 30 VAC
100 m
0.5 mm² (0.8 mm)
0 ... 24 VAC
0 ... 24 VDC
input protected against overvoltage up to 30 VDC and 30 VAC
100 m
0.75 mm² (1 mm)
IP20 (IEC 60529)
V-0 (UL 94)
jet black (RAL9011)
open type equipment for:
indoor use only
pollution degree 2 environment
in control panel:
accessible to authorised personnel only
can be clicked onto horizontally or vertically positioned DIN
rail.
35 x 7.5 (1.38 x 0.30 inches) or 35 x 15 mm (1.38 x 0.59 inches)
(height x depth), in accordance with IEC 60715
0 ... 50 ºC (32 ... 122 °F)
-20 ... 70 ºC (-4 ... 158 °F)
10 % ... 95 % (niet-condenserend)
IEC 61131-2
II
Low Voltage Directive 2006/95/EC:
EN 61010-1 (measurement and control equipment)
EN 61010-2-201 (measurement and control equipment)
EMC Directive 2004/108/EC:
EN 61326-1 (measurement and control equipment)
EN 61000-6-2 (generic immunity standard)
EN 61000-6-3 (generic emission standard)
RoHS directive 2011/65/EU
Installing Priva Compass - 00.014

Advertisement

Table of Contents
loading

Table of Contents