Setting The Weather Interface Wi2 Jumpers - Priva Compass Installation Manual

Table of Contents

Advertisement

Setting the Weather interface WI2 jumpers

The Weather interface has jumpers for setting the type of sensor (Linear light sensor or Radiation
sensor CM3P) and the Radiation sensor factor.
For the Linear light sensor:
1.
Remove jumper J3.
2.
Connect jumper S on J2:
3.
Remove jumper G from J2.
4.
Connect or remove the other jumpers in accordance with the table below and the sensor's
Radiation sensor factor. This value is stated on the supplied calibration certificate.
For the Radiation sensor CM3P:
1.
Remove jumper J3.
2.
Remove jumper S of J2:
3.
Remove jumper G from J2.
4.
Connect or remove the other jumpers in accordance with the table below and the specific
sensitivity of the sensor. This value is stated on the supplied calibration certificate.
Sensor
Sensor
radiation
radiation
factor min
factor max
343.64
338.44
343.64
333.41
338.44
328.49
333.41
323.72
328.49
319.11
323.72
314.63
319.11
310.25
314.63
305.99
310.25
301.86
305.99
297.85
301.86
293.92
297.85
290.09
293.92
286.39
290.09
282.78
286.39
279.12
282.78
275.55
279.12
272.21
275.55
268.94
272.21
265.73
268.94
262.60
265.73
259.56
262.60
256.59
259.56
253.66
256.59
250.81
253.66
248.03
250.81
Installing Priva Compass - 00.014
Jumper A
Jumper B
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
X
-
Jumper C
Jumper D
X
X
X
X
X
X
X
X
X
-
X
-
X
-
X
-
-
X
-
X
-
X
-
X
-
-
-
-
-
-
-
-
X
X
X
X
X
X
X
X
X
-
X
-
X
-
X
-
-
X
-
X
Weather interface WI2
Jumper E
Jumper F
X
X
X
-
-
X
-
-
X
X
X
-
-
X
-
-
X
X
X
-
-
X
-
-
X
X
X
-
-
X
-
-
X
X
X
-
-
X
-
-
X
X
X
-
-
X
-
-
X
X
X
-
61

Advertisement

Table of Contents
loading

Table of Contents