Specifications - Priva Compass Installation Manual

Table of Contents

Advertisement

Priva
Checking by dealer
The Linear light sensor is delivered pre-calibrated. Have the Linear light sensor checked by your
dealer once a year to guarantee correct and accurate measurement.

Specifications

Linear Light Sensor LS2
Article description
Article number
Measurement principle
Spectrum
Peak response
Half angle
Sensitivity
Measurement range
Output range
Supply voltage
Protection
Ambient temperature range
Linear Light Sensor LS2WI (0 ... 50 mV)
Article description
Article number
Measurement principle
Spectrum
Peak response
Half angle
Sensitivity
Measurement range
Output range
Protection
Ambient temperature
66
Linear Light Sensor LS2
3779213
photodiode
525 ... 1100 nm (50 % spectral sensitivity points)
850 nm
60°
33 mV/klux
0 ... 150 klux
0 ... 5 V (not electrically isolated)
21.6 .. 26.4 VDC
short-circuit proof
24 VAC continuous
discharges 900 V/100 nF
-40 ... 80 °C
Linear Light Sensor LS2WI (0 ... 50 mV)
3779205
photodiode
525 ... 1100 nm (50 % spectral sensitivity points)
850 nm
60°
180 ... 340 µV/klux (refer to calibration certificate)
0 ... 160 klux
0 ... 50 mV (depending on sensitivity, refer to calibration certificate)
short-circuit proof
24 VAC continuous
discharges 900 V/100 nF
-40 ... 80 °C