Cross section of the Radiation sensor CM3P
1 Thermopile housing
2 Printed circuit board (9583)
Do not shorten the supplied cable. Coil the remaining length of cable or leave a loop.
Exchanging and calibrating is only possible with an original cable, without additional costs
for replacing the cable.

Connecting

Connect the sensor to a universal input via the Meteorological station interface WI2. See also
Connecting sensors to the Weather interface WI2 (page
Check operation
Check the operation of the sensor in daylight. Use a multimeter to measure the voltage across the
connecting terminals of the I/O module. Depending on the ingress of light, you must measure a
voltage between 0 mV (no light) and 50 mV (a lot of light).
In the Netherlands, the maximum radiation level in the summer is around 1000 W/m
sensitivity value of 18.6 µV/(Wm

Solari CM3P maintenance

Clean the Radiation sensor CM3P at least once per year or more frequently if the Radiation sensor
CM3P begins to provide inaccurate measurements.Clean the unit with a damp cloth and a little mild
detergent if so required.
Do not use aggressive cleaning agents and/or abrasives.
Make sure that no moisture, dirt or dust enters the housing when opening the Radiation
sensor CM3P, since these can be detrimental to the measurement.
When closing the housing, be aware that the cover only fits in one position (tab fits in notch).
Checking by dealer
The Radiation sensor CM3P has been calibrated before delivery. Have the Radiation sensor CM3P
checked by your dealer once a year to guarantee correct and accurate measurement.
68
3 Connector
58).
-2
this results in an output voltage of 18.6 mV.
2
. With a
Installing Priva Compass - 00.014