Universal input - Current measurement
Input current measurement range
Maximum permissible input voltage
Number of measurements per second
Resolution
Accuracy
Input resistance
Protection
Universal input - Measurement of resistance
Measuring range (automatic selection)
Accuracy (nominal, at an ambient temperature of
50 ºC (122 ºF))
Maximum permissible input voltage
Number of measurements per second
Resolution
Maximum permitted capacity at input
Universal inputs - Digital use
Voltage range
Maximum permitted input voltage range
Type of measurements
Minimum detectable pulse width
(Live contact)
Minimum detectable pulse width
(Dry / open collector)
Maximum input frequency
(Live contact, 50% duty cycle)
Maximum input voltage "0"
Minimum input voltage "1"
Current from input with pull-up circuit enabled
132
0 ... 22 mA
26.4 VAC
0 ... 30 VDC
50 @ 50 Hz mains frequency
60 @ 60 Hz mains frequency
2.3 µA (approximately 13 bits over 20 mA)
± (40 μA + 0.4% of measurement)
250 Ω, nominal
resistor for current measurement is switched off automatically in
the event of overvoltage (self-restoring after 5 minutes)
0 ... 2.5 kΩ
0 ... 10 kΩ
± (0.8 Ω + 0.22%
± (1.0 Ω + 0.4%
of the
of the
measurement)
measurement)
26.4 VAC
-24 ... 30 VDC
1 @ 50 Hz mains frequency
1.2 @ 60 Hz mains frequency
approximately 14 bits
10 nF
Alternating current
0 ... 26.4 VAC
0 ... 26.4 VAC
status and pulse
500 ms
(Mechanical and electronic
switch)
-
-
3 VAC
12 VAC
-
0 ... 40 kΩ
0 - 200 kΩ
± (2.3 Ω + 0.41%
± (41 Ω + 1.12%
of the
of the
measurement)
measurement)
Direct current
0 ... 30 VDC
-24 ... 30 VDC
status and pulse
35 ms
(Mechanical and electronic
switch)
1000 ms
(Mechanical and electronic
switch)
14 Hz
(Mechanical and electronic
switch)
3 VDC
12 VDC
-4 mA nominal