Outside Temperature Sensor Ots2; Outside Temperature Sensor; Connecting - Priva Compass Installation Manual

Table of Contents

Advertisement

Priva

Outside temperature sensor OTS2

Outside temperature sensor

The Outdoor temperature sensor contains a temperature-dependent resistor with a negative
temperature coefficient (NTC) in a hermetically-sealed glass tube.
The Outside temperature sensor should preferably be mounted on the Meteorological station and
connected to a Priva process computer.

Connecting

The Outside temperature sensor can be connected both directly to a universal input, or via the
Meteorological station interface WI2.
Direct to universal input
1.
Connect the sensor to a universal input of the Priva Blue ID hardware.
2.
Connect the cable as shown in the table. No need to worry about polarity.
Connection of cable to universal input
Colour
Green
Yellow
White
Brown
Cable type and length
You can extend the cable: feed the cable from the Outside temperature sensor to a junction box
(minimum protection class IP 65) and bridge the distance from the junction box to the computer
with a new shielded cable.
Under no circumstances must you use tape alone to extend the cable.
78
Function
sensor signal
Sensor GND (not electrically isolated)
None
None
Connection
UI
FG
Not connected
Not connected
Installing Priva Compass - 00.014