Specifications of inputs and outputs
The various types of inputs and outputs are available on various modules. The module specifications
indicate which inputs and outputs are available on the module in question. The specifications of the
inputs and outputs are described in this chapter.
Digital inputs
Input voltage measurement range
Maximum permitted input voltage
Type of measurement
Minimum detectable pulse width
(Live contact)
Minimum detectable pulse width
(Dry / open collector)
Maximum input frequency
(Live contact, 50% duty cycle)
Maximum input frequency
(Dry / open collector, 50% duty cycle)
Maximum input voltage for low
Minimum input voltage for high
Input resistor with pull-up circuit disabled
Input resistor with pull-up circuit enabled
Functional isolation of inputs in relation to system
neutral
Maximum current of FG connections
Indication (only for modules with manual override) •
Universal inputs - Analogue use
Type of measurement to be set per input
Mains frequency suppression (NMRR @ 50/60 Hz)
Universal input - Voltage measurement
Measurement range
Maximum permissible input voltage
Number of measurements per second
Resolution
Accuracy
Input resistance
Maximum source resistance
Installing Priva Compass - 00.014
General specifications of Priva Blue ID C-Line controllers and modules
Alternating current
0 ... 30 VAC
0 ... 30 VAC
pulse and status
500 ms
(Mechanical switch)
500 ms
(Electronic switch)
-
-
-
3 VAC
12 VAC
24 kΩ nominal for positive voltages
19 kΩ nominal for negative voltages
-1 mA (low current pull-up)
-5 mA (high current pull-up)
250 V
10 A
green/red LEDs for status of inputs (colour is adjustable)
voltage
current
resistance
-60 dB (applies for a pure sinus)
0 ... 10 V
26.4 VAC
-24 ... 30 VDC
50 @ 50 Hz mains frequency
60 @ 60 Hz mains frequency
14 bits over 12 V (730 µV)
± (5mV + 0.1% of the measurement)
> 1 MΩ
1 kΩ
Direct current
0 ... 30 VDC
-30 ... 30 VDC
pulse and status
10 ms
(Mechanical switch)
350 µs
(Electronic switch)
10 ms
(Mechanical switch)
350 µs
(Electronic switch)
50 Hz
(Mechanical switch)
1,400 Hz
(Electronic switch)
50 Hz
(Mechanical switch)
1,400 Hz
(Electronic switch)
3 VDC
12 VDC