Priva Compass Installation Manual page 136

Table of Contents

Advertisement

Priva
Digital relay outputs
Output configuration
Maximum switching voltage
Maximum switching current
Maximum switching voltage in USA/Canada when
switching different mains voltage phases on the
same module
External fuse
Expected service life of relay contacts with cosφ
= 1 and maximum of 6 switches per minute
Expected service life of relay contacts with cosφ
≠ 1 and maximum of 6 switches per minute
UL certified service life of relay contacts with cosφ
= 1 and maximum of 6 switches per minute
UL certified service life of relay contacts with cosφ
≠ 1 and maximum of 6 switches per minute
Maximum switching frequency
Fail-safe
Indication (for modules with manual override only) •
Controls (for modules with manual override only)
134
normally open contact or changeover contact (depending on
output)
250 VAC (30 VAC when used in Compass)
30 VDC
3 A (cosφ = 1)
125 VAC
8 A maximum
up to 250 VAC and 3 A: 300,000 switches
24 VDC and 3 A: 300,000 switches
250 VAC and 2 A AC15: 200,000 switches
250 VAC motor 370 W AC3: 300,000 switches
24 VDC and 3 A L/R 7 ms: 100,000 switches
24 VDC and 1 A DC13: 200,000 switches
up to 250 VAC and 3 A: 30,000 switches
24 VDC and 3 A: 30,000 switches
240 VAC and 0.5 hp motor: 1,000 switches
120 VAC and 0.25 hp motor: 1,000 switches
B300 pilot duty rating: 6,000 switches
6 times per min.
if communication with the controller fails, the outputs are set to
a user-configured state
green/red LEDs for status of outputs (colour is adjustable)
orange LED for status of control (automatic or manual)
red alarm LED
buttons for manual operation to control connected equipment:
0: relay off
A: automatic or manual control
1: relay on
Installing Priva Compass - 00.014

Advertisement

Table of Contents
loading

Table of Contents